    Accurately test flue gases in furnaces and domestic boilers to determine operation efficiency. Time/date documentation for future reference.

    Measures CO, O2, pressure, and temperature
    Calculates CO2 and gross or net efficiency
    Works on High Efficiency furnace
    Select between 4 fuels (Natural Gas, LPG, Light Oil, Heavy Oil)
    Pump driven for fast response
    Dual input differential manometer with 3 selectable units of measure: kPa, mBar, inH2O
    Flue probe with built-in thermocouple
    IR printer port - use optional A740 Infrared Printer
    Soft carrying case
    Protective rubber boot
  • Tags: Bàn Map
Đơn vị tiền tệ
  • Số lượng:
  • Thành tiền

See Technical Specs for details on TPI-712 upgrade kits

Accurately test flue gases in furnaces and domestic boilers to determine operation efficiency. Time/date documentation for future reference.

  • Measures CO, O2, pressure, and temperature
  • Calculates CO2 and gross or net efficiency
  • Works on High Efficiency furnace
  • Select between 4 fuels (Natural Gas, LPG, Light Oil, Heavy Oil)
  • Pump driven for fast response
  • Dual input differential manometer with 3 selectable units of measure: kPa, mBar, inH2O
  • Flue probe with built-in thermocouple
  • IR printer port - use optional A740 Infrared Printer
  • Soft carrying case
  • Protective rubber boot

Applications:
RESIDENTIAL
  • Furnace
  • Hot water heater
  • Radiant heat boilers
  • CO testing
COMMERCIAL
  • Boilers
  • Furnaces
  • Hot water heater
  • CO testing 
INDUSTRIAL
  • Boilers
  • Furnaces
  • Hot water heater
  • CO and high CO testing
Measure and Memory:
  • CO
    • Range: 0-10,000ppm
    • Resolution: 1ppm
    • Accuracy: ±5ppm or 5%, whichever is greater
  • O2
    • Range: 0-25%
    • Resolution: 0.1%
    • Accuracy: ñ0.3%
  • CO2
    • Range: 0-25%
    • Resolution: 0.001
    • Accuracy: Calculated
  • Excess Air (Calculated)
  • Efficiency (Calculated)
  • Leak (Level)
  • Pressure (Difference)
  • Temperature (2-Channel): -100° - 1,000°C
  • Difference (Ch1-Ch2 Calculated)
  • Single Memory Store: 10
  • Data Logger 100 Steps x 4 Page
  • Recall Function
  • Real Time Display
  • Backlight
  • IR Print Port
  • Store Mode Print
  • Real Mode Print
  • IRDA
Specifications:
  • Operating Temperature Range: -10ø to 50øC (14ø to 122øF)
  • Battery: 4AA Alkaline Batteries
  • Fuels: Natural Gas, LPG, Light Oil, Heavy Oil
  • Display: Backlit LCD T
  • Time & Date: 24 Hour Real-Time Clock
  • Dimensions: 200mm x 90mm x 60mm
  • Weight: 500g
  • Switch Off: Failsafe
  • Exhaust: Safety Spigot
  • Conforms To: BS7927 (and the draft BS7967)

Included with all models: