- Hãng sản xuất: Sonel
- Model: MZC-310S
- Xuất xứ: Ba Lan
The MZC310S is a professional portable meter for testing electrical installations with over-current circuit breakers. The instrument measures short-circuit L-PE, L-N and L-L loop and prospective short-circuit loop current. A measurements can be done either with low testing current (up to 42A) with 2-pole method or high testing current (up to 280A) with 4-pole method that enables measurements with very high accuracy and resolution. The results can be stored in the internal memory and send to a computer via serial interface.
MZC-310S Technical Specifications
Back
Electric security: - type of insulation: double, according to EN 61010-1 and IEC 61557 - measurement category: CAT IV 300V acc. to EN 61010-1 - protection class acc. to EN 60529: IP20 Other technical data: - power supply alkaline batteries LR14 (C) (5 pcs.) - resistor limiting the current: for measurement 4p: 1,5Ω for measurement 2p: 10Ω - number of short circuit loop measurements (alkaline batteries): min. 2000 (4/min.) - temperature coefficient: ±0,1% of measured value /°C Rated operational conditions: - operating temperature: 0...+40°C
Voltages measurement (True RMS)
Range
Resolution
Accuracy
0...440V
1V
±(2% m.v. + 2 digits)
· frequency range: DC, 45...65Hz · input impedance of the voltmeter: >200kΩ
Frequency measurement (for voltages within the range 50...440V)
45,0...65,0Hz
0,1Hz
±(0,1% m.v. + 1 digits)
Short circuit loop parameters measurement using high current (4p, Imax=280A)
High-current of measurement of short circuit loop impedance ZS: measuring range according to IEC61557: 7,2mΩ...1999mΩ
0...199,9mΩ
0,1mΩ
±(2% m.v. + 2mΩ)
200...1999mΩ
1mΩ
Short circuit resistance RS and reactance XS display range
±(2% m.v. + 2mΩ) impedance reading for a particular measurement
Prospective short circuit loop current measuring range according to IEC 61557: for Un = 230V 115,0A...32,0kA for Un = 400V 200A...55,7kA
115,0...199,9A
0,1A
accuracy of the current indication computed, respectively, with the use of resistance measurement
200...1999A
1A
2,00...19,99kA
0,01kA
20,0...199,9kA
0,1kA
200kA...*
1kA
* 230 kA for UL-N 400 kA for UL-L
Measurement of short circuit loop using standard current (2p, Imax=42A)
Touch voltage measurement UST (shock voltage UT)
0...100V
±(10% m.v. + 2 digits)
Short circuit loop impedance ZS measurement: measuring range according to IEC61557: 0,13Ω...199,9Ω for 1,2m long test leads
0,00...19,99Ω
0,01Ω
±(2% m.v. + 3 digits)
20,0...199,9Ω
0,1Ω
±(3% m.v. + 3 digits)
±(2% m.v. + 3 digits) impedance reading for a particular measurement
Prospective short circuit loop current
1,150...1,999A
0,001A
2,00...19,99A
0,01A
20,0...199,9A
20,0...40,0kA