Thiết bị đo vòng lặp Sonel MZC-310S

Có: 0 sản phẩm trong giỏ

Thiết bị đo vòng lặp Sonel MZC-310S
  • Mã SP:
  • Giá NY: Liên hệ
  • Giá bán: Liên hệ
  • Tình trạng:
  • Khuyến mãi:
  • Lượt xem: 3676
  • Tags: Bàn Map
Đơn vị tiền tệ
  • Số lượng:
  • Thành tiền

- Hãng sản xuất: Sonel

- Model: MZC-310S

- Xuất xứ: Ba Lan

 

The MZC310S is a professional portable meter for testing electrical installations with over-current circuit breakers. The instrument measures short-circuit L-PE, L-N and L-L loop and prospective short-circuit loop current. A measurements can be done either with low testing current (up to 42A) with 2-pole method or high testing current (up to 280A) with 4-pole method that enables measurements with very high accuracy and resolution. The results can be stored in the internal memory and send to a computer via serial interface.

 MZC-310S Technical Specifications

 

Back

 

 

  • Measurement of very low short circuit loop impedances (with resolution 0,1mΩ) with a current of 150A at 230V; maximum 280A at 440V or measurement with a current of 23A at 230V; maximum 42A at 440V.
    - measurements in installations with rated voltages between: 220/380V and 230/400V and frequencies 45...65Hz,
    - ability to perform measurements in short circuit system: phase-phase, phase-protective, phase-neutral,
    -  differentiation between the phase voltage and the inter-phase voltage while calculating the shortcircuit current,
    - Ability to change the length of test leads (measurement 23/42A),
    - four-pole method, test leads do not require calibration (measurement 150/280A).
  • Touch voltage and touch shock voltage measurement (with resistor 1kΩ).
  • AC voltage measurement in range 0...440V.
  • Memory for 999 measurement results with an ability to transfer the data to a PC.
  • Meter meets the requirements of the standard EN 61557.

Electric security:
- type of insulation: double, according to  EN 61010-1 and IEC 61557
- measurement category: CAT IV 300V acc. to EN 61010-1
- protection class acc. to EN 60529: IP20

Other technical data:
- power supply     alkaline batteries LR14 (C) (5 pcs.)
- resistor limiting the current:
   for measurement 4p: 1,5Ω 
   for measurement 2p: 10Ω
- number of short circuit loop measurements (alkaline batteries): min. 2000 (4/min.)
- temperature coefficient:  ±0,1% of measured value /°C 

Rated operational conditions:

- operating temperature: 0...+40°C

Voltages measurement (True RMS)

Range

Resolution

Accuracy

0...440V

1V

±(2% m.v. + 2 digits)

 

· frequency range: DC, 45...65Hz
·  input impedance of the voltmeter: >200kΩ

Frequency measurement (for voltages within the range 50...440V)

Range

Resolution

Accuracy

45,0...65,0Hz

0,1Hz

±(0,1% m.v. + 1 digits)

 

 

Short circuit loop parameters measurement using high current  (4p, Imax=280A)

High-current of measurement of short circuit loop impedance ZS:
measuring range according to IEC61557: 7,2mΩ...1999mΩ

Range

Resolution

Accuracy

0...199,9mΩ 

0,1mΩ

±(2% m.v. + 2mΩ)

200...1999mΩ

1mΩ

Short circuit resistance RS and reactance XS display range

Range

Resolution

Accuracy

0...199,9mΩ 

0,1mΩ

±(2% m.v. + 2mΩ)
impedance reading for 
a particular measurement

200...1999mΩ

1mΩ

Prospective short circuit loop current
measuring range according to IEC 61557:
for Un = 230V   115,0A...32,0kA
for Un = 400V   200A...55,7kA 

Range

Resolution

Accuracy

115,0...199,9A

0,1A

accuracy of the current
indication computed,
respectively,
with the use of resistance
measurement

200...1999A

1A

2,00...19,99kA

0,01kA

20,0...199,9kA

0,1kA

200kA...*

1kA

* 230 kA for UL-N
   400 kA for UL-L 

Measurement of short circuit loop using standard current (2p, Imax=42A)

Touch voltage measurement UST (shock voltage UT)

Range

Resolution

Accuracy

0...100V

1V

±(10% m.v. + 2 digits)

Short circuit loop impedance ZS measurement:
measuring range according to IEC61557: 0,13Ω...199,9Ω for 1,2m long test leads

Range

Resolution

Accuracy

0,00...19,99Ω

0,01Ω

±(2% m.v. + 3 digits)

20,0...199,9Ω

0,1Ω

±(3% m.v. + 3 digits)

Short circuit resistance RS and reactance XS display range

Range

Resolution

Accuracy

0,00...19,99Ω

0,01Ω

±(2% m.v. + 3 digits)
impedance reading for 
a particular measurement

20,0...199,9Ω

0,1Ω

±(2% m.v. + 3 digits)
impedance reading for 
a particular measurement

 

 

Prospective short circuit loop current

Range

Resolution

Accuracy

1,150...1,999A

0,001A

accuracy of the current
indication computed,
respectively,
with the use of resistance
measurement

2,00...19,99A

0,01A

20,0...199,9A

0,1A

200...1999A

1A

 2,00...19,99kA

 0,01kA

 20,0...40,0kA

 0,1kA

 

Link Exchange: Duong Ren - Kinh Hien Vi - Panme - Ban Map - Thuoc Cap-